0 installation, 1 connect the cable, 2 prepare the card for configuration – Emerson Liebert IntelliSlot IS-WEB485ADPT User Manual

Page 8: Table 2 communication settings, Nstallation, Table 2, Communication settings, Warning

background image

Installation

4

2.0

I

NSTALLATION

2.1

Install a Liebert IntelliSlot Web Card—Non-Adapter Version

Follow these steps to install a Liebert IntelliSlot Web card (non-adapter version—P/N IS-WEBCARD,

IS-WEBLB and IS-WEBLBDS).
1. Locate the Liebert IntelliSlot option bay on your Liebert equipment—You might need to remove a

plastic cover.

2. Insert the Liebert IntelliSlot Web Card into the Liebert IntelliSlot bay.
3. Secure the card with the supplied screws.
4. Connect an Ethernet cable.

DHCP: The card ships with DHCP service enabled. The MAC address is on a

sticker on the top of the card.

OR

Static IP: To assign a static IP address or hostname, use terminal emulation

software to configure the card, as described in Sections 2.1.1 and 2.1.2.

2.1.1 Connect the Cable

1. Locate the blue serial configuration cable (null modem) that shipped with the

card.

2. Connect the configuration cable to the DB-9 port on the card and to a COM port

on your PC.

2.1.2 Prepare the Card for Configuration

• Use terminal emulation software, such as

Microsoft

®

HyperTerminal, to open a

connection to the card with the settings in

Table 2.

• Press the Enter key for the Main Menu, above

right.

• Select IP Network Settings, then Boot/IP

Settings and follow the instructions to enter

an IP ADDRESS, NETMASK and GATEWAY.

• Press Esc to return to the Main Menu.
• Choose Exit and Save to save your changes

and reboot the card.

!

WARNING

Only a qualified service professional should install these products. Liebert recommends

having a Liebert Services representative perform the installation in large UPSs. Contact

Liebert Services at 1-800-LIEBERT (1-800-543-2378).

Table 2

Communication settings

Baud Rate:

9600

Data Bits:

8

Parity:

None

Stop Bits:

1

Flow Control:

None

NOTE
When installing the card in a Liebert NX

,

configure the communication port of NX to

2400 baud. See the NX user manual for

details.