Configuration Overview

8

3.3

Open the Terminal Emulation Interface - TCP/IP Connection

To access configuration using terminal emulation software with

an Ethernet connection to the Web card:
1. Open a terminal emulation application, such as

HyperTerminal.
To do this:

• Click the Start button, then Programs, Accessories,

Communications and finally HyperTerminal.

2. In the Connection Description window, enter a name for the

connection—for example, GXT2U—then click OK.

3. In the Connect To window:

• Choose TCP/IP (Winsock) from the Connect Using

drop-down list.

• Enter the IP address or hostname of the Web card—for

example, 192.168.0.125—in the Host Address box, then

click OK.

4. When the message at right appears in the HyperTerminal window,

press the Enter key.

5. Enter the Administrator username and password (both are case-

sensitive):
a. Login (username—default is Liebert)
b. Password (default is Liebert)

6. In the Main Menu, enter the number that corresponds to your choice.

Refer to 3.1 - Guide to Configuration for details on each function.

7. After making changes, return to the Main Menu and choose Exit and

Save to reboot the Web card and put your changes into effect (see

3.6 - Saving Changes and Reinitializing the Web Card).

NOTE
For security, change the default username and password (see 5.7 - Change Username /

Password).

Name

TCP/IP

(Winsock)

RTCS v2.96.00 Telnet server

Service Port Manager Active
Ends Session

Login: Liebert
Password: ********

Main Menu
----------
1: System Information
2: IP Network Settings
3: Messaging
4: Factory Settings
5: Firmware Updates

q: Quit and abort changes
x: Exit and save