Installing NIM Cards and Rack Mounting
2-2 Hardware Installation
•
Each XSR AC power supply requires a three-pronged power receptacle capable of delivering
the current and voltage specified in Appendix A. An AC outlet on a separately fused circuit is
required for each XSR to provide power redundancy, and must be located within 182
centimeters (6 feet) from the site. The power cord used and type of outlet is dependent on the
country. In the United States, a power cord with a NEMA 5-15P plug is provided with each
XSR.
•
Ambient temperature at the installation site must be maintained between 0° and 40°C (41° to
104°F). Temperature changes must be maintained within 10°C (18°F) per hour.
Installing NIM Cards and Rack Mounting
Perform the following steps to install optional NIM card(s) and rack mount the XSR:
1.
Be sure the power cord is disconnected before you add a NIM card.
2.
Place the XSR on a flat, static-free surface.
3.
Remove the XSR cover from the chassis, as shown in
, by first removing screws from
the sides and top.