beautypg.com

Important safety instructions, Save these instructions, Mportant – Emerson Liebert Challenger With Liebert iCOM Control 3000/ITR User Manual

Page 7: Afety, Nstructions, Warning

background image

1

I

MPORTANT

S

AFETY

I

NSTRUCTIONS

SAVE THESE INSTRUCTIONS

This manual contains important safety instructions that should be followed during the installation

and maintenance of the Liebert Challenger 3000/Liebert Challenger ITR with Liebert iCOM. Read

this manual thoroughly before attempting to install or operate this unit.
Only qualified personnel should move, install or service this equipment.
Adhere to all warnings, cautions and installation, operating and safety instructions on the unit and in

this manual. Follow all operating and user instructions.

!

WARNING

Risk of electric shock. Can cause injury or death.
Disconnect local and remote power supplies before working within.
Before proceeding with installation, read all instructions, verify that all the parts are included

and check the nameplate to be sure the voltage matches available utility power.
The Liebert iCOM microprocessor does not isolate power from the unit, even in the “Unit Off”

mode. Some internal components require and receive power even during the “Unit Off” mode

of Liebert iCOM control.
The factory-supplied optional disconnect switch is inside the unit. The line side of this switch

contains live high-voltage.
The only way to ensure that there is NO voltage inside the unit is to install and open a remote

disconnect switch. Refer to unit electrical schematic.
Follow all local codes.

!

WARNING

Risk of explosive discharge from high-pressure refrigerant. Can cause injury or death.
This unit contains fluids and gases under high pressure. Relieve pressure before working with

piping.

!

WARNING

Risk of refrigerant system rupture or explosion from overpressurization. Can cause

equipment damage, injury or death.
If a pressure-relief device is not provided with the condenser unit, the system installer must

provide and install a discharge pressure-relief valve rated for a maximum of 500 psig (34bar)

in the high side refrigerant circuit. Do not install a shutoff valve between the compressor and

the field installed relief valve.
One or more additional pressure-relief valves are required downstream of any and all

field-installed isolation valves. Do not isolate any refrigerant circuits from overpressurization

protection.
For systems requiring EU CE compliance (50Hz), the pressure-relief valve must be CE

certified to the EU Pressure Equipment Directive by an EU “Notified Body.”

NOTE
A pressure-relief valve is provided with Liebert Lee-Temp

condensers. A fusible plug is

provided on Liebert Fan Speed Control condensers. The Liebert indoor cooling unit has a

factory-installed high pressure safety switch in the high side refrigerant circuit.