beautypg.com

Table 19 reheat troubleshooting, Table 19, Reheat troubleshooting – Emerson Liebert Challenger With Liebert iCOM Control 3000/ITR User Manual

Page 67

background image

Troubleshooting

61

Excessive arcing in the

canister

Drain valve clogged or

defective

Verify that drain valve operates freely when activated. Clean

valve and replace coil or valve if defective. Flush canister

several times and replace if arcing persists.

Improper water supply

If water is commercially softened, reconnect humidifier to

raw water supply, drain canister, and restart If connected to

hot supply, reconnect to cold water.

Insufficient drain rate

Increase drain rate by adjusting % pot on circuit board

above the preset 70% to roughly 80%.

Excessive iron content in

water

Analyze iron content of water. If it exceeds 0.1 mg./l, install

a filter to remove iron from water supply.

On cold startup, canister

fills, high water alarm

activates and humidifier

fails to reach full amperage

Conductivity of water too low

Drain canister and add one Alka-Seltzer tablet to canister.

Refill. Turn the % pot to roughly 60%. Restart humidifier. If

amperage rises rapidly, it may be necessary to dilute the

water to prevent blown fuses. If it rises too slowly, add

another Alka-Seltzer tablet.

On cold startup, canister

fills, high water alarm

activates and humidifier

fails to reach full amperage

Fill solenoid not closing tightly

If humidifier returns to canister full condition, verity that the

fill solenoid closes tightly.

Table 19

Reheat troubleshooting

Symptom

Possible Cause

Check or Remedy

Reheat will not operate;

contactor not pulling in

Control not calling for heat

Check monitor status.

Reheat safety stat open

Jumper between terminals P34-1 and P34-2. If reheat operates,

safety is open. Remove jumper. Replace safety.

Reheat not operating;

contactor pulling in

Heater burned out

Turn Off power and check heater continuity with Ohm meter.

NOTE:
Reheat element sheaths and fins are manufactured with stainless steel. Regular inspections

are necessary to ensure proper cleanliness of the reheating element. Should inspection reveal

corrosion particles on the reheating element or adjoining surfaces (including ducts and

plenums), appropriate cleaning should be performed. Periodic reheating element replacement

may be required to meet specific application requirements.

Table 18

Steam generating humidifier troubleshooting (continued)

Symptom

Possible Cause

Check or Remedy