Page 16: Liebert icom default home screen—simple view

background image

Liebert iCOM Display Components and Functions

10

Figure 5

Liebert iCOM default home screen—Simple view

4.1.1 Control Interface—Three Main Menus

The Liebert iCOM control has three main menus: User, Service and Advanced.
The User menu contains the most frequently used features, settings and status information. The Ser-

vice menu contains settings and features used to set up unit communications and for unit mainte-

nance. The Advanced menu contains settings used to set up the unit at the factory.

When the buttons on the Liebert iCOM control have not been pressed for a short period, the display

backlight turns Off. Pressing any key will turn the backlight On (wake up the screen) and display the

Status menu of the last cooling unit viewed. The Status menu will show the cooling unit’s operational

mode(s), return air temperature and humidity readings, temperature and humidity setpoints and any

active alarm conditions.
If the cooling unit has a large display and is not on a network, or if the unit has a small display,

whether it is networked or stand-alone, the Status menu will display only that cooling unit’s informa-

tion. Any large display that is connected to a network can be used to view any cooling unit on the net-

work or show an average view of the entire system of cooling units.

NOTE
The Liebert iCOM’s Advanced menu is for factory use only or in consultation with the factory

service department.

NOTE
Menu settings may be viewed without a password, but changing settings requires a password.

If a password is required, the Liebert iCOM shows a prompt to enter the password. The

password for the User menu is 1490. The password for Service menu is 5010. For details on

entering a password, see 4.1.3 - Entering the Password

9/29/2010 08 :28 (01) MSG UNIT ON
9/29/2010 08 :27 (01) MSG POWER ON

UNIT 1

9/29/2010 09 :18:07

50

72.0°F

74.1

°F

50%

51.6

°F

%

SET

ACT

72%

100%

UNIT ON

for nex t / pr ev uni t for s y s tem v i ew
for menu for previous screen ? for help

E S C

52.0°F

03/2011

System or

Unit # view

Temperature

Sensor Reading

Evaporator

Fan Speed

Percent

Cooling

Next

Maintenance

Date and

Time

Return Air

Temperature

Setpoint

Return Air

Humidity

Setpoint

Humidity Sensor

Reading

Supply Air Setpoint

Supply

Air Temperature

System (or Unit)

On/Off

Most Recent

Alarms

(Date, Time, Unit,

Description)