2 optional alarms, 1 loss of water flow, 2 smoke detected – Emerson Liebert Challenger With Liebert iCOM Control 3000/ITR User Manual

Page 41: 3 standby gc pump on, 4 standby unit on, 5 water under floor, 3 set alarms—user menus, Table 3 set alarms—user menus, Optional alarms, Loss of water flow

background image

Alarm Descriptions

35

6.2

Optional Alarms

6.2.1 Loss of Water Flow

Available only with 3-way valves and occurs when no water flow is detected in the chilled water or

condenser water supply line. An optional flow switch is required for this alarm. Check for service

valves closed, pumps not working, etc.

6.2.2 Smoke Detected

Smoke is detected in the return air by an optional Liebert Smoke Detector. Check for source of smoke

or fire, and follow appropriate emergency procedures.

6.2.3 Standby GC Pump On

The primary pump has failed, and the standby pump is activated (glycol cooled and GLYCOOL units

only).
Check for problems with the primary pump (fuses blown, motor burnout, service valve shut, stuck

check valve, impeller damage, etc.).

6.2.4 Standby Unit On

The primary environmental control system has had an alarm condition, and the standby system is

activated.

6.2.5 Water Under Floor

Water is detected by an optional Liebert Water Detection System. Check under the raised floor for

water or other leaks.

6.3

Set Alarms—User Menus

NOTE
The alarms are specified by the customer at the time of order. All alarms will report to a

Liebert remote monitoring unit. Additional devices and wiring may be required at the factory

for some of the alarms.

Table 3

Set alarms—User Menus

Large Display

Small

Display

Alarm Description

Range

Large

Display

Range

Small

Display

Res.

Std.

U201

PASSWORD

-

-

-

-

-

-

U202

Return Sensor

Alarms

RTN SNSR

Std. Sensor

Alarms Enable

0 = Disabled

1 = Enabled

0 = No,

1 = Yes

-

Enabled

U203

High Return

Temperature

HI TEMP

Std. Sensor High

Temperature Alarm

34-210 °F

(1-99°C)

34-210 °F

1-99°C

1

80°F

27°C

U204

Low Return

Temperature

LO TEMP

Std. Sensor Low-

Temperature Alarm

34-210 °F

(1-99°C)

34-210 °F

(1-99°C)

1

65°F

18°C

U205

High Return

Humidity

HI HUM

Std. Sensor High-

Humidity Alarm

1-99%

1-99%

1

60%

U206

Low Return

Humidity

HI HUM

Std. Sensor Low

-Humidity Alarm

1-99%

1-99%

1

40%

U207

Sensor A

Alarms

SENSOR A

Sensor A

Alarms Enable

0 = Disabled

1 = Enabled

0 = No,

1 = Yes

-

Disabled

U208

High-Temperature

Sensor A

HI TEMPA

Sensor A

High-Temperature Alarm

34-210 °F

(1-99°C)

34-210 °F

(1-99°C)

1

90°F

32°C

U209

Low Temperature

Sensor A

LO TEMPA

Sensor A Low-

Temperature Alarm

34-210 °F

(1-99°C)

34-210 °F

(1-99°C)

1

55°F

13°C

U210

High Humidity

Sensor A

HI HUM A

Sensor A

High-Humidity Alarm

1-99%

1-99%

1

70%

U211

Low Humidity

Sensor A

LO HUM A

Sensor A

Low-Humidity Alarm

1-99%

1-99%

1

30%