beautypg.com

11 compressor oil, Table 10 compressor oil types, 5 compressor replacement – Emerson Liebert Challenger With Liebert iCOM Control 3000/ITR User Manual

Page 53: Before replacing or returning a compressor, 1 compressor functional check, Compressor replacement, Compressor functional check, Table 10, Compressor oil types, Notice

background image

Component Operation and Maintenance

47

7.4.11 Compressor Oil

NOTICE

Risk of improper compressor lubrication. Can cause compressor and refrigerant system

damage.
Failure to use oil types, viscosities and quantities recommended by the compressor

manufacturer may reduce compressor life and void the compressor warranty. See oil types

specified in Table 10.

• Do NOT mix polyol ester (POE) and mineral-based oils.
• Do NOT mix oils of different viscosities.

Consult Emerson or the compressor manufacturer if you have questions.

1. Use Copeland POE Oil ULTRA 22CC, Mobil EAL Arctic 22CC or other Copeland-approved oils.

7.5

Compressor Replacement

Replacement compressors are available through your local Emerson office. Compressors are shipped

in reusable packaging. If unit is under warranty, complete and include Liebert Service Credit Appli-

cation (LSCA) with the compressor that is being returned. The original compressor should be

returned in the same packaging.

Before Replacing or Returning a Compressor

Be certain that the compressor is actually defective. At a minimum, recheck a compressor returned

from the field in the shop or depot for Hipot, winding resistance and ability to start before returning

it. More than one-third of compressors returned for warranty analysis are determined to have nothing

wrong. They were misdiagnosed in the field as being defective. Replacing working compressors unnec-

essarily costs everyone.

7.5.1 Compressor Functional Check

The following diagnostic procedure should be used to evaluate whether the compressor is working

properly.
1. Proper voltage to the unit should be verified.
2. The normal checks of motor winding continuity and short to ground should be made to determine

if the inherent overload motor protector has opened or if an internal motor short or ground fault

has developed. If the protector has opened, the compressor must be allowed to cool sufficiently to

allow it to reset.

3. Proper indoor and outdoor blower/fan operation should be verified. Condenser glycol flow should

be verified.

4. With service gauges connected to suction and discharge pressure fittings, turn On the compressor.

If suction pressure falls below normal levels, either the system charge is low on or there is a flow

blockage in the system.

5. If suction pressure does not drop and discharge pressure does not rise to normal levels, reverse

any two of the compressor power leads and reapply power to make sure compressor was not wired

to run in reverse direction. If pressures still do not move to normal values, system is properly

charged and solenoid valves function, the compressor is faulty. Reconnect the compressor leads as

originally configured and use normal diagnostic procedures to check operation of the reversing

valve.

6. To test if the compressor is pumping properly, the compressor current draw must be compared to

published compressor performance curves using the operating pressures and voltage of the

system. If the measured average current deviates more than ±15% from published values, a faulty

compressor may be indicated. A current imbalance exceeding 15% of the average on the three

phases should be investigated further.

Table 10

Compressor oil types

Compressor Type

R-407c

Copeland Scroll

and Digital Scroll

POE Oil - ISO 22

Viscosity

1