MODBUS REGISTERS
EATON Power Xpert
®
Gateway Series 1000 Card User’s Guide
S 164201670 Rev 1
61
For example, the AC Voltage between Phase A and Neutral is available
in register 4010. To read the AC Voltage in Phase A at Panel #1, set the
Modbus program to Unit ID 2 and register 4010:
IP:
Unit ID: 2
Starting Register: 4010
Number of Registers: 2
Function Code: 04
To read the AC Voltage in Phase A at Panel #4, set the Modbus program
to Unit ID 5 and register 4010:
IP:
Unit ID: 5
Starting Register: 4010
Number of Registers: 2
Function Code: 04
Table 5. Panel Summary Registers (FC 04)
Name
Register
Data Type
Bytes
Display Template
1000
UINT
2
Vendor Name
1001
STRING
64
Model Name
1033
STRING
64
Display Name
1065
STRING
64
Serial Number
1123
STRING
64
Device Volts Rating
1202
UINT
4
Number of Phases
1208
UINT
2
Asset ID
1324
STRING
128
Breaker Rating
1453
UINT
2
Breaker Warning
1456
UINT
2
Breaker Overload
1457
UINT
2
Neutral Current Alarm
1459
UINT
2
Enter Admin State
3047
UINT
2
Enter Operating State
3048
UINT
2
Enter Readiness State
3049
UINT
2
Enter Alarm State
3050
UINT
2
Enter Standby State
3051
UINT
2