GETTING STARTED
EATON Power Xpert
®
Gateway Series 1000 Card User’s Guide
S 164201670 Rev 1
7
6.
Verify that the PDU is turned on.
7.
After a few seconds, press Enter. The Network Settings menu
appears in approximately one minute (see Figure 7).
---------------------------------------------------------
---------------- Network Settings ----------------
---------------------------------------------------------
1. Ethernet Port 1 Settings
2. Ethernet Port 2 Settings
3. DNS Server (Primary)
: [None]
4. DNS Server (Secondary) : [None]
5. Reset to Factory Defaults and Exit
0. Exit
Select an option ==> 1
Figure 7. Network Settings Menu
If the menu does not appear, press Enter again. If it still does not
appear, check the following conditions:
S
Verify the serial line is set to 9600 baud, No parity, 8 data bits,
1 stop bit, and no flow control.
S
If the serial line settings are correct, check the cabling to verify
all connections are secure.
S
Verify that your terminal program is on the correct
communication port for the serial connection.
S
Verify that the card has power (one or more LEDs on the card
are illuminated). The PDU should be on.
8.
Continue to the following section, “IP Address Assignments.”