MODBUS REGISTERS
EATON Power Xpert
®
Gateway Series 1000 Card User’s Guide
S 164201670 Rev 1
60
Table 4. PDU/RPP Alarms (FC 02) (continued)
Data Type
Register
Name
Branch Breaker Overload Warning
1249
BOOL
Branch Breaker Overload
1250
BOOL
Branch Breaker Disconnected
1252
BOOL
Main Breaker Overload Warning
1253
BOOL
Main Breaker Overload
1254
BOOL
Primary Breaker Open
1256
BOOL
Primary Breaker Tripped
1257
BOOL
Secondary Breaker Open
1258
BOOL
Secondary Breaker Tripped
1259
BOOL
Input Phase Rotation
1477
BOOL
Panel Registers and Alarms
This section contains information for the Panel Summary Registers
(FC 04) and the Panel Alarms (FC 01 or 02).
Panel Summary Registers (FC 04)
NOTE The panel can be wired for either a wye (phase to neutral) or a delta
(phase-to-phase) configuration. The registers contain only the data supported by the wired
configuration. For example, if the panel is wired in a wye configuration, the voltages AN, BN,
and CN are available, but the voltages AB, BC, and CA are not available (an exception code is
returned). Refer to the actual panel for the wiring configuration.
Table 5 shows the registers that contain summary data for the panel.
The registers contain the total information for all the breakers in the
panel.