MODBUS REGISTERS
EATON Power Xpert
®
Gateway Series 1000 Card User’s Guide
S 164201670 Rev 1
54
PDU/RPP Registers and Alarms
This section contains information for the PDU/RPP Registers (FC 04) and
PDU/RPP Alarms (FC 02).
PDU/RPP Registers (FC 04)
To read the vendor name in the PDU/RPP, set the Modbus program to
Unit ID 1 and register 1001:
IP:
Unit ID: 1
Starting Register: 1001
Number of registers: 32
Function Code: 04
The PDU/RPP returns 32 registers containing up to 64 characters. There
are two ASCII characters per register, so the vendor name could be
displayed as POWERWARE.
Table 3. PDU/RPP Registers (FC 04)
Name
Register
Data Type
Bytes
Vendor Name
1001
STRING
64
Model Name
1033
STRING
64
Display Name
1065
STRING
64
Device Type
1097
UINT
4
Device ID
1099
UINT
4
Device Guid
1103
STRING
40
Serial Number
1123
STRING
64
Conn Style
1159
UINT
2
Device Comm Address
1160
STRING
64
Device Baud Rate
1192
UINT
4
Time Sync Period
1194
UINT
4
Data Update Period
1196
UINT
4
Device VAR Rating
1198
UINT
4
Device Volts In Rating
1204
UINT
4
Device Volts Out Rating
1206
UINT
4