Troubleshooting

LEDs

The AN-X-PBSLV has LEDs that indicate the state of the Ethernet
connection, the connection to the PROFIBUS network processor, and the
overall module state.

Ethernet LEDs

There are two LEDs that indicate the state of the Ethernet connection.

The orange LED, labelled 100, is on if the link is running at 100
Mbits/second and is off otherwise.

The green Link/Act LED is off if the link is inactive and is on if the link
is active. If activity is detected, the link blinks at 30 ms intervals and
continues blinking as long as activity is present.

SYS LED

The SYS LED is used by the AN-X operating system and software to
indicate the state of operations and errors.

Use it in conjunction with the logs to locate the cause of problems.

In the following, red 3 means three red flashes followed by a pause, and
so on.

SYS LED State

Possible cause

Red 2

AN-X is in config mode

Red 3

DHCP configuration failed

Red 4

Fatal application error, check logs for cause

Red 5

Application memory access violation, check logs

Red 6

Application failed, illegal instruction, check logs

Red 7

Application crashed, unknown cause, check logs

Fast red flash

PROFIBUS configuration failed

Configuration of ControlLogix support failed

Configuration of AN-X to AN-X communication
failed

Single red flash

AN-X to AN-X communication problem, error
on producer or timeout on consumer

ControlLogix scheduled data or unscheduled
messaging, addressing or connection problem