beautypg.com

Unscheduled messages, Pccc/plc-5 files – ProSoft Technology AN-X-PB User Manual

Page 49

background image

AN-X-PBSLV Page

43

January 2008

Unscheduled Messages

You can use unscheduled messages to access the PROFIBUS data
directly on the AN-X-PBSLV:

directly, from a computer or PLC, by sending messages

from a DDE or OPC server, such as RSLinx

from an HMI such as RSView or Wonderware InTouch, using
the appropriate driver

PCCC/PLC-5 Files

The module "emulates" PLC-5 integer files.

The AN-X-PBSLV supports Word Range read/write, Typed read/write,
Read/Modify/Write, and PLC-3 Bit Write messages, with both logical
ASCII and logical binary addressing.

Data is mapped in two different ways – on a node-by-node basis and
packed into blocks.

Node-by-node Mapping

The node-by-node mapping is more convenient for obtaining data for a
given node but is less efficient. It requires a separate read to obtain data
for each node.

PLC-5 Files

Description

N200-N325

Node 0-125 Outputs from PROFIBUS master

N400-N525

Node 0-125 Inputs to PROFIBUS master (active nodes
only)

N600-N725

Node 0-125 Inputs to PROFIBUS master (monitored
nodes only)

Packed Mapping

The packed mapping is more efficient – the data is packed into a small
number of files, but processing is required to extract the data for any
specific node. Also, if the configuration changes, the addresses for the
data for each node will change.

PLC-5 Files

Description

N20-N39

Node 0-125 Outputs from PROFIBUS master

N40-N59

Node 0-125 Inputs to PROFIBUS master (active nodes