PROFIBUS Configuration

GSD File

The GSD file for the AN-X-PBSLV is provided on the distribution CD
and on the AN-X module itself.

To access the GSD file on the AN-X, run the web interface (see page
58). At the bottom of the home page, there is a link: AN-X-PBSLV GSD
File
. To view the GSD file, click on this link. To save the GSD file to
your computer, right click on this link and select Save Target As…

Configuring Slaves on the AN-X-PBSLV

You configure the slaves that the AN-X module is emulating or
monitoring on PROFIBUS by creating a comma separated variable
(CSV) file using either a text editor or a spreadsheet such as Excel, then
sending the configuration to AN-X using the AN-X web interface.

The configuration file defines the network baud rate and the properties of
the PROFIBUS slaves the AN-X module is emulating or monitoring.

Baud Rate

The baud rate is defined by a line with the keyword BaudRate in the first
field and an entry that selects the baud rate in the second field.

Possible entries for the baud rate value are:

Baud rate

File entry

12 Mbps

12m

6 Mbps

6m

3 Mbps

3m

1.5 Mbps

1m5

500 Kbps

500k

93750 bps

93k75

19200 bps

19k2

9600 bps

9k6

Examples:

BaudRate, 12m

BaudRate, 9k6