beautypg.com

ProSoft Technology AN-X2-GENI User Manual

Page 60

background image

Page

54

AN-X2-GENI (AN-X-GENI/B)

May 2013

Debug Mode

SYS or MS LED

The SYS or MS LED is used by the AN-X operating system and software to indicate the
state of operations and errors.

The SYS or MS LED should be used in conjunction with the logs to locate the cause of
problems.

SYS (or MS) LED State

Possible cause

Flashing red/green

Unscheduled messaging, addressing or connection problem

Flashing red/off

Configuration file problem

NET or NS LED

– Network Status

The NET (or NS) LED shows the status of Genius I/O communication.

Color

Meaning

Flashing or solid red One or more configured Genius blocks is not active on the

network

Network error (CRC, stop, abort, etc.)

Baud rate mismatch

Yellow

No configured Genius I/O, and no Genius network activity

Green

All configured blocks are active on the Genius bus

Some blocks may be in error

Fatal Errors

AN-X2 monitors its operation for “impossible” conditions and generates a fatal error if it
detects one. It generates a fatal error code on the SYS (or MS) LED by flashing 8 bits
followed by a pause. The least significant bit is first, with green for 1 and red for 0.

If a fatal error occurs, record the SYS (or MS) LED sequence and contact technical
support.