beautypg.com

Example configuration file – ProSoft Technology AN-X2-GENI User Manual

Page 35

background image

AN-X2-GENI (AN-X-GENI/B) Page

29

Example Configuration File

Example Configuration File:

;QTS AN-X2-GENI Scan Configuration Utility

;Copyright (c) 2005 Quest Technical Solutions

;Auto Config Ethernet/IP File

;ScanGeniProg

ClxName,AnxGeniMas

ClxPrefix,GENI_

ClxSlot,0

DataOutput ; Outputs from ControlLogix

,b1,b01_Out, ; Ofs= 0 Len= 1 IC660BBR101 16-Ckt Normally-open Relay Block

,b2,b02_Out, ; Ofs= 1 Len= 1 IC660BBD020 24/48VDC 16 Ckt Source I/O Block

,b3,b03_Out, ; Ofs= 2 Len= 2 IC660BBA020 24/48VDC 4In/2Out Analog Block

,b9,b09_Out, ; Ofs= 4 Len=12 IC670GBI001 Genius Bus Interface Unit

,b22,b22_Out, ; Ofs= 16 Len= 2 IC660BBD024 12/24VDC 32 Ckt Source I/O Block

,GlobSend; Global Data Sent by AN-X2-GENI

DataInput ; Inputs to ControlLogix

,BlockErr ; Map BlockErr here since Clx sets to -0xffffffff on Connection Failure

,b1,b01_Inp, ; Ofs= 2 Len= 1 IC660BBR101 16-Ckt Normally-open Relay Block

,b2,b02_Inp, ; Ofs= 3 Len= 1 IC660BBD020 24/48VDC 16 Ckt Source I/O Block

,b3,b03_Inp, ; Ofs= 4 Len= 4 IC660BBA020 24/48VDC 4In/2Out Analog Block

,b9,b09_Inp, ; Ofs= 8 Len=12 IC670GBI001 Genius Bus Interface Unit

,b16,b16_Inp, ; Ofs= 20 Len=32 IC693BEM331 Series 90-30 Bus Controller

,b22,b22_Inp, ; Ofs= 52 Len= 2 IC660BBD024 12/24VDC 32 Ckt Source I/O Block

,b31,b31_Inp, ; Ofs= 54 Len=32 IC697BEM731 Series 90-70 Bus Controller

;The following map 'Ghost Mode' Monitored Outputs to ClxSlot 8

;They must be 'uncommented' for 'Ghost Mode' Monitoring

;ClxSlot,8 ; This maps monitored 'Ghost Mode' outputs to Slot 8

;DataInput ; Inputs to ControlLogix