Diagnostics and Troubleshooting

PDPS ♦ ProLinx Gateway

PROFIBUS DP Slave

ProSoft Technology, Inc.

Page 35 of 61

December 31, 2008

4.2

Base Module LEDs

LED State

Description

Off

Power is not connected to the power terminals. This LED is hardware
driven, so it only requires power to operate.

Power

Green Solid

Power is connected to the power terminals. Verify that the other LEDs
for operational and functional status.

Off Normal

operation.

Fault

Red Solid

A critical error has occurred. Program executable has failed or has
been user-terminated and is no longer running. Press Reset p/b or
cycle power to clear error. If not, use the Debug procedures described
later in this manual.

Off Normal

operation.

Cfg

Amber Solid

The unit is in the configuration mode. The configuration file is being
read and the unit is implementing the configuration values and
initializing the hardware. This will occur during power cycle, or after
pressing the reset button. It also occurs after a cold/warm boot
command is received.

Off Normal

operation.

Flashing

An error condition has been detected and is occurring. Check
configuration.

Err

Solid Red

This condition is indicative of a large number of errors in the application
interface communications. The module's error flag is cleared at the
start of each command (master/client) or receipt of data
(slave/adapter/server).

4.3

PROFIBUS Slave LED Indicators

Active LED

Error LED

Description

On Off Normal

Operation

Off

Off

Module not receiving power or program terminated

Off

On

Module configured and waiting for first output data set.

Flashing

On

PROFIBUS communication problem (not receiving output)

Off

Flashing

User timeout expired.

On

Rapid Irregular
flash

Configuration problem from master.

Flashing Together

Configuration error during initialization.

Flashing Alternately

Watchdog timer expired.

4.4 Definition

of

Module's

Extended Diagnostics Data

The Extended Diagnostic Data is reported during startup and initialization
sequence when the master requests diagnostic data from the module. The
Extended Diagnostics is "Device Related" type providing status data (the
extended diagnostic bit 3 in standard diagnostic byte 1 is set = 0). The data
length is normally 14 (0E) bytes displayed in the following format:

Byte(s) Description

(HEX)

0

Extended Diagnostics length (normally 14 bytes (0E))

1 to 6

ASCII data for Product Version

7 to 10

ASCII data for Product Name

11

Value of Status Register [0] (see Section 2)