Configuration PDPS

♦ ProLinx Gateway

PROFIBUS DP Slave

ProSoft Technology, Inc.

Page 27 of 61

December 31, 2008

3.3.5 Comm

Timeout

Multiplier

1 to 10

This parameter sets the communication timeout value for the module. The value
entered is multiplied by 125 milliseconds to determine the actual timeout value.
For example, a value of 1 specifies a communication timeout of 125 milliseconds.

3.3.6 Use Database Paging

Yes or No

This Parameter Enables or disables user access to the PDPS's Database area
outside the section reserved for the PROFIBUS Protocol in the range of Word
400 to Word 3999.

3.4 Set_Param

(SAP61)

ProSoft PROFIBUS Slave (PDPS) devices have a configurable parameter for
SPC3 User Prm Byte. The following illustrations show the value of this parameter
in Sycon, the configuration tool for ProLinx PROFIBUS Master devices, and in
ProSoft Configuration Builder for PROFIBUS, the configuration tool for ProSoft
PROFIBUS Master devices.