Downloading a file from pc to the module – ProSoft Technology 5205-DFNT-PDPS User Manual
Page 29

Configuration PDPS
♦ ProLinx Gateway
PROFIBUS DP Slave
ProSoft Technology, Inc.
Page 29 of 61
December 31, 2008
Byte 7
Spec_User_Prm_Byte
Bit Name
Significance
Default
State
0
Dis_Startbit
The start bit monitoring in the receiver
is switched off with this bit
Dis_Startbit = 1,
That is, start bit monitoring is switched off.
1
Dis_Stopbit
Stop bit monitoring in the receiver is
switched off with this bit
Dis_Stopbit = 0
That is, stop bit monitoring is not switched
off.
2
WD_Base
This bit specifies the time base used to
clock the watchdog.
WD_Base = 0: time base 10 ms
WD_Base = 1: time base 1 ms
WD_Base = 0
That is, the time base is 10 ms.
3 to 4
Res
To be parameterized with 0
0
5
Publisher_Enable
DXB-publisher-functionality of the
SPC3 is activated with this bit
Publisher_Enable = 0, DXB-request-
telegrams are ignored;
Publisher_Enable = 1, DXB-request-
telegramme are processed
6 to 7
Res
To be parameterized with 0
0
3.5
Downloading a File from PC to the Module
To download a file from the Configuration Builder to the module:
1 Verify that your PC is connected to the module with a null-modem serial cable
connected to the serial port on your PC and the serial port on the module
2 Open the Project Menu, and then choose Module.
3 On the Module menu, choose Download. Wait while ProSoft Configuration
scans for communication ports on your PC. When the scan is complete, the
Download dialog box opens.
4 Select the port to use for the download.
5 Click the Download button.