Mailbox structure, Mailbox, Structure – ProSoft Technology 5205-DFNT-PDPS User Manual

Page 19

background image

Functional Overview

PDPS ♦ ProLinx Gateway

PROFIBUS DP Slave

ProSoft Technology, Inc.

Page 19 of 61

December 31, 2008

2.5 Mailbox

Structure

This 200 Byte Array is located in the PLC containing the PDPM gateway module,
not in the PDPS.

Example Raw Database Exchange. Output from PLC to PDPM

Word

Start
Byte

End
Byte

Description

0 0 150 (Raw data write).This value tells PDPS driver to write into

Database paging section.

0

1 1 160 (Raw data read). This value tells PDPS driver to read from

Database Paging section.

1 2 3 Start register in database for write. This value tells the PDPS driver

where in the Database Paging section to start writing to.

2 4 5 Number of registers to write (1 to 94). This value tells the PDPS

Driver the quantity of registers to be filled with data.

3 6 7 Start register in database for read. This value tells the PDPS driver

where in the Database Paging section to start reading from.

4 8 9 Number of registers to read (1 to 96). This value tells the PDPS

Driver the quantity of registers to read from.

5 to 98

10

197

Words to write to the database. The actual data to be transferred to
the Database paging section. In the PLC, fill these bytes of the
Array with values to be transferred to the PDPS's Database paging
section.

198 198 Reserved.

Do not use.

99

199 199 150 (Raw data write). This value tells PDPS driver to write into

Database paging section. Duplicated from Array[0] index.

Example Response Block From PDPM. Input to PLC from PDPM.
Communications acknowledgement.

Word

Start
Byte

End
Byte

Description

0 0 160 (Raw data read). PDPS Driver responded to the PDPM driver

which in turn responded to the PLC that the data in this 200 word
Array is from the PDPS drive's Database paging section.

0

1 1 150 (Raw data write). PDPS driver is responding to the PDPM

driver which in turn responds to the PLC that the data has been
written.

1 2 3 Start register in database for read. PDPS driver is responding to the

PDPM driver which in turn responds to the PLC where in the PDPS
Database paging was the beginning of the data read.

2 4 5 Number of registers to read (1 to 96). This value tells the PLC the

quantity of registers that the PDPS Driver read.

3 to 98

6

197

Words read from the database. The actual words that were
readfrom the PDPS Database Paging section.

99 198 199 Reserved. Do not use.

199

199

160 (Raw data read). Signifies the end of the read block