Mailbox from plc to gateway, Mailbox from gateway to plc, Example raw database exchange – ProSoft Technology 5205-DFNT-PDPS User Manual
Page 20: Example response block from gw, 1 mailbox from plc to gateway, 2 mailbox from gateway to plc, 3 example raw database exchange, 4 example response block from gw

PDPS ♦ ProLinx Gateway
Functional Overview
PROFIBUS DP Slave
Page 20 of 61
ProSoft Technology, Inc.
December 31, 2008
2.5.1 Mailbox From PLC to Gateway
Start Byte
End Byte
Description
0
0
Block number of data in block
1
1
Block number of data requested
2
198
Data for block
199
199
Block number of data in block
2.5.2 Mailbox From Gateway to PLC
Start Byte
End Byte
Description
0
0
Block number of data in block
1
1
Block number last requested by PLC
2
198
Data for block
199
199
Block number of data in block
2.5.3 Example Raw Database Exchange
Start Byte
End Byte
Description
0
0
150 (Raw data write)
1
1
160 (Raw data read)
2
3
Start register in database for write
4
5
Number of registers to write (1 to 94)
6
7
Start register in database for read
8
9
Number of registers to read (1 to 96)
10
197
Words to write to the database
198 198
Reserved
199
199
150 (Raw data write)
2.5.4 Example
Response Block From GW
Start Byte
End Byte
Description
0
0
160 (Raw data read)
1
1
150 (Raw data write)
2
3
Start register in database for read
4
5
Number of registers to read (1 to 96)
6
197
Words read from the database
198 198
Reserved
199
199
160 (Raw data read)