Diagnostics and Troubleshooting

PROFIBUS DP Slave

Page 36 of 61

ProSoft Technology, Inc.

December 31, 2008

Byte(s) Description

(HEX)

12

Value of Status Register [1] (see Section 2)

13

Module State (see Section 2)

Bytes 7 through 10 Data - Specific Product Code Value

Each ProLinx application has its own, unique product code. You can determine
the product code from the Version screen in the Configuration/Debug menu.

The following table lists the product codes for some ProLinx modules that
support the PDPS protocol.

Example Product

Example Product Code

5105-ASCII-PDPS ASPS

5105-DFCM-PDPS DFPS

5105-DH485-PDPS D4PS

5105-DNPM-PDPS DMPS

5105-DNPS-PDPS D3PS

5105-I101S-PDPS ISPS

5105-I103M-PDPS PSI3

5105-MCM-PDPS PDSM

Sample Diagnostics reported to master.

Translated as follows:

Extended diagnostics length 0E= 14 bytes, Product Version 56 = "V", 30 =
"0", 31 = "1", 2E = ".", 30 = "0", 35 = "5", Product Name 50 = ""P", 44 = ""D", 53
= "S", 34 = "4" (MVI46),

Status Register [0] 41 = SPC3 in passive idle and WD-State is in DP_Control
State, Status Register [1] 03 = 1.5 Baud rate, Module State 04 = not in data
exchange