Port physical and protocol specifications, Profibus slave port specifications – ProSoft Technology 5205-DFNT-PDPS User Manual
Page 16

PDPS ♦ ProLinx Gateway
Functional Overview
PROFIBUS DP Slave
Page 16 of 61
ProSoft Technology, Inc.
December 31, 2008
2.2
Port Physical and Protocol Specifications
2.2.1 PROFIBUS Slave Port Specifications
Type Specifications
General Parameters
Internal Database
Up to 4000 registers (words) available.
GSD File
Downloadable from ProSoft-Technology.com web
site
PROFIBUS Slave
Communication parameters
Baud Rate: 9.6 kbps to 12 Mbps
Supported I/O length
122 words Input data
122 words Output data
200 words max
Supported PROFIBUS DP features
Freeze Mode
Sync Mode
Auto Baud Setting
Configurable Parameters
a) PROFIBUS Node Address: 0 to 125
b) Data byte swapping
c) Action on loss of PROFIBUS connection
d) Comm Fail Timeout Multiplier
e) Status Data location in Internal Database
Status Data
Error codes available on an individual command
basis. In addition, a slave status list is maintained
per active PROFIBUS Slave port.
Physical Connection
PROFIBUS Connector
Standard PROFIBUS DB-9F communication
connector. Cable connection matches PROFIBUS
pin out specification.
Important Note: The slave node address is set to 126 by default in the module configuration file
(page 21). The default node address must be changed to a valid address between 0 to 125 by the
user for the slave to function on the PROFIBUS network.