ProSoft Technology MVI46-103M User Manual
Page 92

MVI46-103M ♦ SLC Platform
Reference
IEC 60870-5-103 Master Communication Module
Page 92 of 187
ProSoft Technology, Inc.
September 12, 2006
# 176 Transformer differential protection
# 192 Line Differential protection
# 255 Global function type
#
# Database Index = Database address in module
#
# ASDU Database Function Point
# Type Index Code Index
START
2 640 128 74
2 656 128 75
2 672 128 76
2 688 128 77
2 704 128 78
2 720 128 79
2 736 128 80
2 752 128 81
2 768 128 82
2 784 128 83
2 800 128 84
2 816 128 85
2 832 128 86
2 848 128 87
2 864 128 88
2 880 128 89
2 896 128 90
2 912 128 91
2 880 128 89
2 896 128 90
3 60 128 144
3 64 128 145
3 68 128 146
3 72 128 147
END
# This section is used to define session 0 which runs on Port 1
[IEC-103 Master Session 1]
Communication Port : 0 #Index of COM port for session (0 or 1)
Sector Count : 5 #1 is max value for this version of app
Data Link Address : 1 #Range is 0 to 65535 DL address of slave
Failure Delay : 10 #Min Sec to delay before poll of offline slave
#(0 to 2000 seconds)
Confirm Timeout : 1000 #0 to 2^32-1 mSec to wait for DL confirm
Retry Count : 0 #0 to 255 retries for if no confirm
Response Timeout : 20000 #Timeout for confirm of req (0 to 2^32-1)
C1/C2 Poll Count Pend : 5 #class 1 or 2 polls before next slave tried (0-
65535)
Class 1 Polls : 0 #Max class 1 polls to this session
Class 1 Pend delay : 0 #Min mSec delay between call (0 to 2^32-1)
Class 2 Pend delay : 0 #Min mSec delay between call (0 to 2^32-1)
Class 1 Poll delay : 0 #Min mSec delay between call (0 to 2^32-1)
Class 2 Poll delay : 0 #Min mSec delay between call (0 to 2^32-1)