Measurands, Generic functions, Information numbers used in control direction – ProSoft Technology MVI46-103M User Manual
Page 167: System functions, 5 information numbers used in control direction

Reference MVI46-103M
♦ SLC Platform
IEC 60870-5-103 Master Communication Module
ProSoft Technology, Inc.
Page 167 of 187
September 12, 2006
Fun
128 160 176 192 254 255
Inf Description
GI Type
t(z) l>>
∆l
T
∆l
L
GEN GLB
130
AR
blocked
X 1 X X X
Measurands
Fun
128 160 176 192 254 255
Inf Description
GI Type
t(z) l>>
∆l
T
∆l
L
GEN GLB
144 measurand I
3.1
X
X
145 measurands I, V
3.2
X
X
146 measurands I, V, P, Q
3.3
X
147 measurands
I
N
, V
EN
3.4
X X
148 measurands
I
L1,2,3
, V
L1,2,3
, P, Q, f
9
X
Generic functions
Fun
128 160 176 192 254 255
Inf
Description
GI
Type
t(z)
l>>
∆l
T
∆l
L
GEN GLB
240 read headings of all defined groups
10
X
241 read values or attributes of all entries of
one group
10
X
243 read directory of a single entry
11
X
244 read value or attribute of a single entry
(x)
10
X
245 end of general interrogation of generic
data
10
X
249 write entry with confirmation
10
X
250 write entry with execution
10
X
251 write entry aborted
10
X
7.8.5
Information Numbers Used In Control Direction
System functions
Fun
128 160 176 192 254 255
Inf Description
Type
t(z) l>>
∆l
T
∆l
L
GEN GLB
0
initiation of general interrogation
7
X
0
time synchronization
6