Word Offset in
Block
Data Field(s)
Description
4100
Block ID
This field contains the block identification code of 9901
for the block.
4101
Command Count
This field defines the number of user commands
contained in the block. The valid range for the field is 1
to 8.
4102 to 4111
Command #1
Data required to build the user defined command in the
command queue.
4112 to 4121
Command #2
Data required to build the user defined command in the
command queue.
4122 to 4131
Command #3
Data required to build the user defined command in the
command queue.
4132 to 4141
Command #4
Data required to build the user defined command in the
command queue.
4142 to 4151
Command #5
Data required to build the user defined command in the
command queue.
4152 to 4161
Command #6
Data required to build the user defined command in the
command queue.
4161 to 4171
Command #7
Data required to build the user defined command in the
command queue.
4172 to 4181
Command #8
Data required to build the user defined command in the
command queue.
The following fields are used for each 10-word record in the command list:
Word Offset
Definitions
Description
0
Database Index
Address in module to associate with the command.
1 Session
Index
Session index defined in the module to associate with
the command.
2
Sector Index
Sector index for session as defined in the module.
3
Data Type
ASDU data type associated with the command.
4
Function Code
Function Code for the command.
5
Point Index *
*Information
Number
Information object address for the point on which the
command operates.
6
Override Flag
Override flag for general command.
7
Override Value
Override value for general command.
8
Reserved
Reserved for future use.
9
Reserved
Reserved for future use.
Refer to the command list section of this documentation for a detailed definition
of the fields contained in this block. They are the same as those used in
constructed the commands in the command list.
There is no response block built by the module to send back to the processor
after the block is processed. The module will set register 4100 to a value of zero
after the commands have been processed. The commands are placed in the
command queue and issued at a high priority.