Slc interface, Hardware specifications, Hardware – ProSoft Technology MVI46-103M User Manual
Page 8: Specifications

MVI46-103M ♦ SLC Platform
Product Specifications
IEC 60870-5-103 Master Communication Module
Page 8 of 187
ProSoft Technology, Inc.
September 12, 2006
Connections:
1 - RJ45 RS-232 Configuration Tool Connector
2 - RJ45 RS-232/422/485 Application ports
1.1.2 SLC
Interface
Operation via simple ladder logic
Complete set up and monitoring of module through RSLogix 500 software
and user constructed configuration file (IEC103M.CFG)
SLC backplane interface via M-File access
All data related to the module is contained in user data files to ease in the
monitoring and interfacing with the module
Control of module and controlled devices on serial network available from
ladder logic
1.2 Hardware
Specifications
The MVI46-103M module is designed by ProSoft Technology and incorporates
licensed technology from Rockwell Automation (SLC backplane technology).
Current Loads:
800 ma @ 5V (from backplane)
Operating Temperature: 0 to 60°C (32 to 140°F)
Storage Temperature:
–40 to 85°C (–40 to 185°F)
Relative Humidity:
5 to 95% (non-condensing)
Configuration Connector: RJ45 RS-232 Connector (RJ45 to DB-9 cable
shipped with unit)
Application Port Connector: RJ45-RS-232/422/485 Connector (RJ45 to DB-9
cables shipped with unit)