General commands, Generic functions, Type 1 - time-tagged – ProSoft Technology MVI46-103M User Manual
Page 168

MVI46-103M ♦ SLC Platform
Reference
IEC 60870-5-103 Master Communication Module
Page 168 of 187
ProSoft Technology, Inc.
September 12, 2006
General commands
Fun
128 160 176 192 254 255
Inf Description
Com Type
t(z) l>>
∆l
T
∆l
L
GEN GLB
16 auto-recloser
on/off
On/Off
20 X X X
17 teleprotection on/off
On/Off 20
X
X
18 protection
on/off
On/Off
20 X X X X
19 LED
reset
On 20 X X X X
23 activate characteristic 1
On
20
X
24 activate characteristic 2
On
20
X
25 activate characteristic 3
On
20
X
26 activate characteristic 4
On
20
X
Generic functions
Fun
128 160 176 192 254 255
Inf
Description
Type
t(z)
l>>
∆l
T
∆l
L
GEN GLB
240 read headings of all defined groups
21
X
241 read values or attributes of all entries of
one group
21
X
243 read directory of a single entry
21
X
244 read value or attribute of a single entry
21
X
245 general interrogation of generic data
21
X
248 write entry
10
X
249 write entry with confirmation
10
X
250 write entry with execution
10
X
251 write entry abort
10
X
7.8.6 Definition
and
Presentation of ASDU'S In Monitor
Direction
Type 1 - Time-tagged
Bytes Description
Spec
1
Value of 1
1 0x81
1 COT
1
Common address of ASDU
1 Function
Type