Mvi46-103m configuration file example, Mvi46-103m, Configuration file example – ProSoft Technology MVI46-103M User Manual
Page 86

MVI46-103M ♦ SLC Platform
Reference
IEC 60870-5-103 Master Communication Module
Page 86 of 187
ProSoft Technology, Inc.
September 12, 2006
7.5 MVI46-103M
Configuration File Example
This section contains a listing of an example IEC103M.CFG file for the MVI46-
103M module.
# IEC103M.CFG
#
# Example file for use with the IEC-870-5-103 Master protocol driver on the
# MVI46 platform (two master ports).
#
[Backplane Configuration]
Module Name : MVI46-103M DEMO MODULE
Failure Flag Count : 0 #Determines if BP failure will cause protocol to be
#disabled (0=Ignore, >0 = failure count to disable)
Pass-Through Events : Y #Pass event messages to processor
# This is the configuration for the IEC-870-5-103 master port emulated on the
# module.
[IEC-870-5-103 Master]
Session Count : 1 #1 to 32 - maximum number of slaves on all channels
[IEC-870-5-103 Master Port 0]
# Communication Parameters
Baud Rate : 19200 #Baud rate for port 110-115200
Parity : E #N=None, O=Odd, E=Even, M=Mark, S=Space
RTS On : 0 #0-65536 mSec before message
RTS Off : 0 #0-65536 mSec after message
Minimum Delay : 10 #Minimum # of mSec before response sent
Receive Timeout : 2000 #Maximum mSec from first char to last to wait
# These parameters are protocol specific
Single char ACK F0,1 or 3 : Y #Single E5 resp to ACK func 0, 1 & 3 req (Y/N)
[IEC-870-5-103 Master Port 1]
# Communication Parameters
Baud Rate : 19200 #Baud rate for port 110-115200
Parity : E #N=None, O=Odd, E=Even, M=Mark, S=Space
RTS On : 0 #0-65536 mSec before message
RTS Off : 0 #0-65536 mSec after message
Minimum Delay : 5 #Minimum # of mSec before response sent
Receive Timeout : 1000 #Maximum mSec from first char to last to wait
# These parameters are protocol specific
Single char ACK F0,1 or 3 : Y #Single E5 resp to ACK func 0, 1 & 3 req (Y/N)
# This section is used to define session 0 which runs on Port 0
[IEC-103 Master Session 0]
Communication Port : 0 #Index of COM port for session (0 or 1)
Sector Count : 5 #5 is max for this version of app
Data Link Address : 0 #Range is 0 to 65535 DL address of slave
Failure Delay : 3 #Min Sec to delay before poll of offline slave
#(0 to 2000 seconds)