[Section]/Item

Value

Range

Description

Minimum

Command Delay:

0 to

65535

This parameter specifies the number of milliseconds to wait
between issuing each command. This delay value is not

applied to retries.

Command Error

Pointer:

-1 to 3995 This parameter sets the address in the internal Modbus

database where the command error data will be placed. If the

value is set to -1, the data will not be transferred to the

database.

Response

Timeout:

0 to

65535

This parameter represents the message response timeout
period in 1-ms increments. This is the time that a port

configured as a master will wait before re-transmitting a
command if no response is received from the addressed

slave. The value is set depending upon the communication

network used and the expected response time of the slowest

device on the network.

Retry Count:

0 to 10

This parameter specifies the number of times a command will

be retried if it fails.

Error Delay

Count:

0 to

65535

This parameter specifies the number of polls to skip on the

slave before trying to re-establish communications. After the
slave fails to respond, the master will skip commands to be

sent to the slave the number of times entered in this

parameter.

[Modbus Slave]

Configuration header for Modbus slave.

Internal Slave ID:

0 to 255

This parameter defines the virtual Modbus slave address for
the internal database. Any requests received by the port with

this address will be processed by the module. Verify that

each device has a unique address on a network.

Bit Input Offset:

0 to 3995 This parameter specifies the offset address in the internal

Modbus database for network requests for Modbus function 2
commands. For example, if the value is set to 150, an

address request of 0 will return the value at register 150 in

the database.

Word Input Offset:

0 to 3995 This parameter specifies the offset address in the internal

Modbus database for network requests for Modbus function 4

commands. For example, if the value is set to 150, an
address request of 0 will return the value at register 150 in

the database.

Output Offset:

0 to 3995 This parameter specifies the offset address in the internal

Modbus database for network requests for Modbus function

1, 5, or 15 commands. For example, if the value is set to 100,

an address request of 0 will return the value at register 100 in

the database.

Holding Register

Offset:

0 to 3995 This parameter specifies the offset address in the internal

Modbus database for network requests for Modbus function
3, 6, or 16 commands. For example, if the value is set to 50,

an address request of 0 will return the value at register 50 in

the database.

Use Guard Band

Timer

Y or N

This parameter specifies if the packet Guard Band is to be

used. This is used for multi-drop only.

Guard Band

Timeout

0 to

65535

This parameter specifies the Guard Band time between
packets in multi-drop slave mode. A value of 0 uses the

default time. A value of 1 to 65535 sets the time in

milliseconds.