MVI94-MCM ♦ Flex I/O Platform

Reference

Serial Communications Modbus Communication Module

User Manual

ProSoft Technology, Inc.

Page 81 of 109

March 29, 2011

Pass-Through Block 9956, 9957, 9958, or 9960 from Module to Processor

Word

Description

0

This word contains the block 9956 to 9958 representing the type of pass-through data

being transferred.

1

This word contains the number of data registers being transferred.

2

This word contains the destination address for the data.

3

This word contains the register data. - For 9960: AND Mask

4

This word contains the second register data when floating-point data is being

transferred. - For 9960: OR Mask

5

Reserved

6

Reserved

Warm Boot Block (9998)
This block does not contain any data. When the processor places a value of

9998 in word 0 of the output image, the module will perform a warm-start. This

involves clearing the configuration and all program status data. Finally, the

program will load in the configuration information from the Flash ROM and begin

running. There is no positive response to this message other than the status data

being set to zero and the block polling starting over.

Cold Boot Block (9999)
This block does not contain any data. When the processor places a value of

9999 in word 0 of the output image, the module will perform a hardware restart.

This will cause the module to reboot and reload the program. There is no positive

response to this message other than the status data being set to zero and the

block polling starting over.