Write Floats to Slave Device
To issue a Write command to Floating-Point addresses, use the configuration in

the following table. The table describes the Modbus Map for the Slave device.

Value

Description

Type

40261

KW

Demand (power)

Float. upper 16 bits

40263

VAR

Reactive Power

Float. upper 16 bits

40265

VA

Apparent Power

Float. upper 16 bits

40267

Power Factor

Float. upper 16 bits

40269

VOLTS

Voltage, line to line

Float. upper 16 bits

40271

VOLTS

Voltage, line to neutral

Float. upper 16 bits

40273

AMPS

Current

Float. upper 16 bits

You must use a COP

statement to copy the data from floating-point data tags

within the ControlLogix processor, into the MCM.DATA.W

RITE

D

ATA

array used

by the MVI94-MCM module. Below is an example.

The length of this COP statement must now be 14. This will COP as many of the
MCM_F

LOAT

_D

ATA

values required to occupy the MCM.D

ATA

.W

RITE

D

ATA

array

for a length of 14. This will take 7 registers, MCM_F

LOAT

_D

ATA

[0]

TO

[6],

and

place that data into MCM.DATA.W

RITE

D

ATA

[0]

TO

[13].

You must configure the command to write all 7 floats (14 Modbus addresses) as

follows.

The above command will take the data from MCM.DATA.W

RITE

D

ATA

[0]

TO

[13]

and write this information to the Slave device node #1 addresses 40261 to

40274.