ProSoft Technology MVI94-MCM-MHI User Manual
Page 27

MVI94-MCM ♦ Flex I/O Platform
Configuration
Serial Communications Modbus Communication Module
User Manual
ProSoft Technology, Inc.
Page 27 of 109
March 29, 2011
Along with the Function Code 3, DevAddress 256 will read Modbus address
40257 of the Slave device. The above command will read 40257 and 40258 of
the Modbus Slave #1 and place that data in MCM.DATA.R
EAD
D
ATA
[0] and [1].
Within the controller tags section of the ControlLogix processor, it is necessary to
configure a tag with the data type of "REAL" as shown in the following illustration.
[+]
Energy_Consumption
REAL[1]
Float
Copy data from the MCM.DATA.R
EAD
D
ATA
[0] and [1]
into the tag
E
NERGY
_C
ONSUMPTION
that has a data type of REAL. Use a COP
statement
within the ladder logic. Here is an example.
Because the tag MCM.DATA.R
EAD
D
ATA
[0] should only be used within the above
command, an unconditional COP statement can be used.
Notice the length of the COP statement is a value of 1. Within a Rockwell
Automation processor, a COP statement will copy the required amount of
"Source" values to fill the "Dest" tag for the Length specified.
Therefore, the above statement will copy ReadData[0] and [1] to fill the 32 bits
required for the tag "Energy_Consumption".
Note: Do not use a MOV statement. A MOV will convert the data from the Source register to the
destination register data type. This would create a data casting statement and will result in the loss
or corruption of the original data.