5.4.2 Read Coil Status (Function Code 01)
Query
This function allows the user to obtain the ON/OFF status of logic coils used to
control discrete outputs from the addressed Slave only. Broadcast mode is not
supported with this function code. In addition to the Slave address and function
fields, the message requires that the information field contain the initial coil
address to be read (Starting Address) and the number of locations that will be
interrogated to obtain status data.
The addressing allows up to 2000 coils to be obtained at each request; however,
the specific Slave device may have restrictions that lower the maximum quantity.
The coils are numbered from zero; (coil number 1 = zero, coil number 2 = one,
coil number 3 = two, and so on).
The following table is a sample read output status request to read coils 0020 to
0056 from Slave device number 11.
Adr
Func
Data Start Pt Hi
Data Start Pt Lo
Data # Of Pts Ho Data # Of Pts Lo
Error Check Field
11
01
00
13
00
25
CRC