Backplane Data Transfer

MVI56-BAS ♦ ControlLogix Platform

User Manual

BASIC Module (DB/BAS Compatible)

Page 44 of 234

ProSoft Technology, Inc.

December 13, 2011

40 PUSH I: REM INPUT BUFFER ADDRESS
50 CALL 14
60 POP Y: REM INPUT BUFFER VALUE AT ADDRESS I
65 X = I - 200
70 PRINT "VALUE AT [", X, "] = ", Y
80 NEXT I
90 END

CALL 56 transfers up to 100 words from a CLX data file to the MVI56-BAS input

buffer using Class 3 message instructions.
Ladder logic must execute a MSG instruction prior to CALL 56 execution in order

to move the data to a temporary buffer. The MSG should have the following

parameters:

The following ladder logic writes the data that will be read by CALL56.

After the ladder logic execution, a CALL 56 can be performed in order to transfer

the data to the MVI56-BAS input buffer.

1 REM CALL 56
10 PUSH 10
20 CALL 56
30 POP X
40 PRINT X