CIP MSG Parameterization

Parameter

Value

Remarks

Message Type

CIP Generic

Service Type

Custom

Service Code

64 hex

Service Code "Bridge Message"

Class

65 hex

CIP Object "CIP_MSG_BRIDGE"

Instance

1

Attribute

0

Source Element

DiagReq

Reference to a Tag of type DPS_DIAGNOSTIC_REQUEST

Destination

DiagCnf

Reference to a Tag of type DPS_DIAGNOSTIC_CONFIRM

Source Length

16 … 48

Corresponds to the size of the DPS_DIAGNOSTIC_REQUEST structure

DPV1 Messaging

This section describes DPV1 messaging functions supported by the PROFIBUS
Slave module.

Note: Every DPV1 read or write request has to be acknowledged by the PLC application program.
Otherwise the PROFIBUS master shuts down communication for both channels, V0 (cyclic IO

data) and V1 (non-cyclic messages). This can cause unexpected lost of data between the master

and the PS69-DPS slave.

DPV1 Class 1 Read Response
The DPV1 Class 1 Read Response message is used by the Slave to reply to a
Master DPV1 Read Request. The MSG instruction Request/Confirmation format
is as follows.