beautypg.com

ProSoft Technology PS69-DPS User Manual

Page 57

background image

PS69-DPS ♦ CompactLogix or MicroLogix Platform

Diagnostics and Troubleshooting

Profibus DP Slave Communication Module

User Manual

ProSoft Technology, Inc.

Page 57 of 108

May 9, 2014

4.1.3 PS69 LEDs

The LEDs as shown on the front panel will be used to indicate status information
of the PS69-DPS Slave module. Each LED has a specific function during Run
time, configuration download, and error indications. The following table shows
the reaction of each during these states for the Slave.

LED

Color

State

Description

SYS

Yellow

Flashing cyclic at
1Hz

Device is in boot loader mode and is waiting for firmware
download.

Yellow

Flashing cyclic at
5Hz

Firmware download is in progress.

Yellow

Flashing irregular (*) Hardware or runtime error detected.

Green

Static On

Slave in cyclic data exchange with DP Master.

Green

Flashing cyclic at
5Hz

Slave has no cyclic data exchange with DP Master.

Green

Flashing irregular (*) Power Up: Configuration missing or faulty, device needs

commissioning.
Runtime: Host Watchdog timeout

Off

Off

Device has no power supply or hardware defect or PLC holds
the module in reset.

COM

Green

On

Slave has received parameter data/configuration data from

the DP Master and has reached the state of data exchange.

Red

On

unused

Off

Off

Slave has not reached the state data exchange.

(*) 3 times fast at 5 Hz, 8 times between 0,5Hz and 1Hz