beautypg.com

ProSoft Technology PS69-DPS User Manual

Page 19

background image

PS69-DPS ♦ CompactLogix or MicroLogix Platform

Start Here

Profibus DP Slave Communication Module

User Manual

ProSoft Technology, Inc.

Page 19 of 108

May 9, 2014

3 Set the Module Properties values as follows:

Parameter

Value

Name

Enter a module identification string. Example: PS69DPS

Description

Enter a description for the module. Example: Profibus DP
Slave Communication Module.

Comm Format

Select Data-INT

Slot

Enter the slot number in the rack where the PS69-DPS
module will be installed.

Input Assembly Instance

101

Input Size

190

Output Assembly Instance

100

Output Size

124

Configuration Assembly Instance

102

Configuration Size

32

4 On the Connection tab, check or un-check, as desired the Major fault option.