beautypg.com

ProSoft Technology PS69-DPS User Manual

Page 77

background image

PS69-DPS ♦ CompactLogix or MicroLogix Platform

Reference

Profibus DP Slave Communication Module

User Manual

ProSoft Technology, Inc.

Page 77 of 108

May 9, 2014

MSB := Module Status Bits

Bit Offset

Structure Member

Data Type

Description

0

Reserved

BOOL

Reserved

1

Reserved

BOOL

Reserved

2

Reserved

BOOL

Reserved

3

Reserved

BOOL

Reserved

4

Reserved

BOOL

Reserved

5

COM

BOOL

Communication

6

RUN

BOOL

Run

7

RDY

BOOL

Ready

RDY (Ready)
When this bit is set, the module is operational. The RDY-Bit should always be set
by the module. If this bit is not set a system error has occurred and the
communication between controller and module is not possible.
RUN (Run)
When the RUN-bit is set, the module is ready for communication. Otherwise an
initialization error or incorrect Parameterization occurs.
COM (Communication)
When this bit is set, the communication is started and the module is engaged in
cyclic data exchange with the Master.

These three bits are the most important bits that the controller application can
use to monitor the communication and operating status of the module

Firmware Revision
This data field, which is part of the input image of the PROFIBUS Slave module,
will contain the current firmware revision. The Minor revision indication will be in
the low byte and the Major revision will be in the high byte. The Firmware Field is
placed in the Input area as shown in the following table.

Byte Offset

Structure Member

Data Type

Description

4

FwMinor

SINT

Firmware Minor Revision

5

FwMajor

SINT

Firmware Major Revision

6-7

Reserved

INT

Reserved

Example:

If FwMajor = 10 and FwMinor = 1 then the firmware revision is 10.1.