ProSoft Technology PS69-DPS User Manual
Page 43
PS69-DPS ♦ CompactLogix or MicroLogix Platform
Configuration and Start-Up
Profibus DP Slave Communication Module
User Manual
ProSoft Technology, Inc.
Page 43 of 108
May 9, 2014
2.2.2 Expansion General Configuration
Fill in the values on the Expansion General Configuration tab as shown in the
following illustration.
Expansion General Configuration
Value
Vendor
283
Product Type
12
Product Code
4
Series/Major Rev/Minor Rev
A
Input Words
(68 + X ) ... 190
Output Words
(2 + Y ) ... 124
Extra Data Length
32
X = Number of Words configured for slave modules (PROFIBUS output data).
The output size can range from 68 to 190 words.
Y = Number of Words configured for slave modules (PROFIBUS input data). The
input size can range from 2 to 124 words.
Vendor Name / Product Type / Product Code for the PS69-DPS module are
283,12,4.
Input Size: This value must be large enough to accommodate 68 words (136
bytes) of status information required by the module, plus the number of words
of PROFIBUS output data. You can increase the size of this area using the
size of each Output module connected. The PROFIBUS Output data image
starts with Word 68 (Byte 136).
Output Size: This value must large enough to accommodate 2 Words (4
Bytes) of command information required by the module, which is 2 Words (4
bytes), plus the number of words of PROFIBUS input data. You can increase
the size of this area using the size of each Input module connected. The
PROFIBUS Input data image starts with byte 4.
Configuration Size: The size for the configuration array must be always 32
Words.
Note: If the parameters do not correspond to the template values, then the controller cannot
establish communication with the module.