ProSoft Technology PS69-DPS User Manual
Page 40

Configuration and Start-Up
PS69-DPS ♦ CompactLogix or MicroLogix Platform
User Manual
Profibus DP Slave Communication Module
Page 40 of 108
ProSoft Technology, Inc.
May 9, 2014
2.1.2 Module Properties 1
The communications parameters for the module should be set as shown in the
dialog below.
Select a name and enter a short description for the module. Select the slot
number in which the module is installed in the controller. Select Data - INT as the
Comm_Format. Set the connection parameters as they are shown in the dialog.
Connection Parameter
Assembly Instance
Size (in Words)
Input
101
68 + X ... 190
Output
100
2 + Y... 124
Configuration
102
32
X = Number of words configured for slave modules (PROFIBUS output data);
output size can be in the range between 68 and 190 words
Y = Number of words configured for slave modules (PROFIBUS input data); input
size can be in the range between 2 and 124 words
Input Size: The input size must be at least 68 Words (136 Bytes). It must be
large enough to accommodate the status information required by the module,
which is 68 Words (136 Bytes) plus the number of PROFIBUS output data.
The user can increase the size of this area using the size of each Output
module connected. The PROFIBUS Output area starts with Word 68 (Byte
136).
Output Size: The output size must be at least 2 Words (4 Bytes). It must be
large enough to accommodate the command information required by the
module, which is 2 Words (4 bytes), plus the number of PROFIBUS input
data. The user can increase the size of this area using the size of each Input
module connected. The PROFIBUS Input data image starts with byte 4.
Configuration Size: The size for the configuration array must be always 32
Words.
Note: If the parameters do not correspond to the template values, then the controller cannot
establish communication with the module.
Select Next >> for the next configuration dialog.