RA 19-7B 011409

2-13

2.4.2.3.2 PARALLEL CONFIGURATIONS USING EXTERNAL WIRES TO CONNECT SENSE LINES

IN PARALLEL AND EXTERNAL WIRES TO CONFIGURE LOCAL SENSING

Figure 2-8 is a simplified diagram of a typical parallel configuration using local sensing via exter-
nal wires to connect V(+) to S(+), V(–) to S(–) and jumpers connected to the I/O mating con-
necter to connect the sense leads in parallel. This configuration requires the following:

1. For each supply in parallel set DIP switch positions 1 and 2 to OFF (open) (see Figure 2-1).

2. For each DIP switch between parallel-connected slots, set DIP switch positions 3 and 4 to

OFF (open) (sense leads will be connected in parallel in steps 8 and 9) (see Figure 2-1).

3. For each DIP switch between parallel-connected slots configure position 5 to connect the

current share bus by referring to PAR. 2.4.2.2.

4. Locate DIP switch(es) at both ends of the parallel group and set positions 3, 4, and 5 to OFF

(open) to isolate the group. (see Figure 2-1).

5. Configure Positions 6, 7, and 8 (alarms) of each DIP switch per PAR. 2.4.4.

6. Connect wire between I/O mating connector pin Sense (+) and corresponding power supply

V (+) terminal at DC OUTPUT terminal block.

7. Connect wire between I/O mating connector pin Sense (–) and corresponding power supply

V (–) terminal at DC OUTPUT terminal block.

8. Connect short jumper across I/O mating connector Sense (+) pins.

9. Connect short jumper across I/O mating connector Sense (–) pins.

FIGURE 2-8. TYPICAL PARALLEL CONNECTIONS USING EXTERNAL WIRES FOR LOCAL SENSING

AND I/O MATING CONNECTOR JUMPERS TO PARALLEL SENSE WIRES