2 parallel operation, 1 parallel dc output connections, 2 parallel current share connections – KEPCO RA 19-7B Operator Manual User Manual

Page 20: Parallel operation -8, Parallel dc output connections -8, Parallel current share connections -8

background image

2-8

RA 19-7B 011409

2.4.2

PARALLEL OPERATION

HSF power supplies having identical voltage ratings can be connected in parallel to provide
redundant operation or increased output current to a common load. The power leads must be
connected in parallel externally (see PAR. 2.8.4.1). (Configurations using internal parallel busing
of the power leads are also possible; consult Kepco’s Applications Engineering for details.)
Three things must be considered when configuring the rack adapter for parallel operation:

• DC OUTPUT

• CURRENT SHARE

• SENSE

2.4.2.1

PARALLEL DC OUTPUT CONNECTIONS

The power leads must be connected in parallel externally (see PAR. 2.8.4.1). DC Output V(+)
and V(–) must be connected in parallel at the DC OUTPUT terminal block (see Figures 2-5
through 2-10).

2.4.2.2

PARALLEL CURRENT SHARE CONNECTIONS

The Current Share pins of the HSF power supplies must be connected together for parallel
operation. This can be done either internally using the DIP switches to configure adjacent slots
in parallel (PAR 2.4.2.2.1), or externally by wiring the I/O mating connector for configuring slots
1, 3, 4, and 6 (PAR. 2.4.2.2.2).