Hree, Single phase, Technical data table – Riello UPS Sentinel Dual (High Power) (3.3 - 10 kVA) User Manual

Page 84: Echnical data table

background image

84

T

ECHNICAL DATA TABLE

T

HREE

/

SINGLE PHASE

UPS

TECHNICAL DATA TABLE

MODELS

SDL 6500 TM

SDL 8000 TM

SDL 10000 TM

INPUT (3 Ø + N star-configured voltages)

Nominal voltage

220/230/240 Vac

Accepted range

0 - 280 Vac

Voltage range for non-intervention of battery

Maximum voltage 276Vac

Minimum voltage:

from 184 to 138 Vac from 100% to 50% of the linear load

Return of operation from mains at 190Vac

Nominal frequency

50 - 60 Hz ±5Hz

Maximum current (1)

13A

15A

19A

Nominal current

(2)

9A

11A

14A

Power factor

0.95

Current distortion @ max load

26%

BYPASS (on L1)

Voltage range accepted for switching

180 - 264 Vac

Frequency range accepted for switching

Frequency selected ±5%

Switching time

0.1ms

BATTERY

Recharge time (8)

6-8 h

OUTPUT

Nominal voltage

220/230/240 Vac selectable ±1.5%

Static variation (3)

1.5% (7)

Dynamic variation (4)

5% in 20ms

Waveform

Sinusoidal

Voltage distortion @ linear load

3%

Voltage distortion @ distorting load

6%

Frequency (5)

50 o 60 Hz selectable

Current crest factor

3 : 1

Nominal power (VA)

6500

8000

10000

Nominal power (W)

5850

7200

9000

Short circuit current

1.5 x In for t= 0.5sec

SUNDRY

Leakage current to earth

10mA

AC/AC performance

92%

Ambient temperature (6)

0 – 40 °C

Humidity

< 90% non condensing

Protections

excessive battery discharge - overcurrent - short circuit - overvoltage -

undervoltage - thermal

Hold-up time

40msec

Noise

< 45 dB(A) at 1mt.

Dimensions H x L x D (mm)

2 x [455mm (19”) x 175mm (4U) x 660mm (26”)]

Weight in Kg (estimated)

approx 28 + 63 Kg

approx 29 + 65 Kg

approx 30 + 65 Kg

(1) @ nominal load, minimum voltage of 180Vac, battery charging
(2) @ nominal load, nominal voltage of 230Vac, battery charging
(3) Mains/Battery @ load 0% -100%
(4) @ Mains/battery/mains @ resistive load 0%/100%/0%
(5) If the mains frequency is within ±5% (user definable) of the selected value, the UPS is synchronized with the mains. If the

frequency is out of tolerance or in operation from battery, the frequency is the selected value ±0.1%

(6) 20 - 25 °C for extended battery life
(7) Recalibration may be necessary after a long period of operation, in order to maintain the output voltage within the indicated

range.

(8) Time needed to reach 90% of charge (after a full discharge at load ≥80%)