Digital lines chapter 6 – Remote Processing RPC-2300 User Manual
Page 20
DIGITAL LINES
CHAPTER 6
Page 18
RPC-2300
High cur rent outpu ts at J3 port A are option ally
configurable as TTL I/ O by replacing U20 with a DIP
shunt jumper. This keeps logic com patible with ports B
and C. If opto channels 8-15 are used as inputs, then
U20 must be replaced by a DIP shunt jumper.
Configuring digital I/O lines
Lines are configured during progr am execution using the
CONF IG PIO command. On power up or reset, all lines
are inputs.
When a line is configured as an output, it can sink a
maximum of 2. 5 mA at 0. 4V and can source a minimum
of 2.5 ma at 2. 4V. W hen driving opto modules, the
outputs sink 15 mA at 1.0V.
Digital I/ O prog ramm ing exam ple
The follow ing exam ple read s a switch at po rt A, bit 3
(J2-25), reads an opto module at channel 1 and writes an
opto module at channel 5. A LE D is controlled at J2-10
(port B, bit 0).
200 D = BIT(0,3)
:'Read switch status, port A
210 F = OPTO(101)
:'read opto module, ch. 1
220 OPTO 103,ON
:'write module, channel 3
230 BIT 1,0,0
:'turn on led at J2-10
240 BIT 1,0,1
:'turn off led at J2-10
250 A = LINE(103)
:'Reads pin 3 at J2
Conne ctor pin ou t - J2
Pin #
82C55
Description
Opto
Channel
19
Port A, line 0
8
21
Port A, line 1
9
23
Port A, line 2
10
25
Port A, line 3
11
24
Port A, line 4
12
22
Port A, line 5
13
20
Port A, line 6
14
18
Port A, line 7
15
10
Port B, line 0
16
8
Port B, line 1
17
4
Port B, line 2
18
6
Port B, line 3
19
1
Port B, line 4
20
3
Port B, line 5
21
5
Port B, line 6
22
7
Port B, line 7
23
13
Port C, line 0
Lower C
0
16
Port C, line 1
Lower C
1
15
Port C, line 2
Lower C
2
17
Port C, line 3
Lower C
3
14
Port C, line 4
Upper C
4
11
Port C, line 5
Upper C
5
12
Port C, line 6
Upper C
6
9
Port C, line 7
Upper C
7
26
Ground
2
+ 5V