Appendix A CX-10 Modbus Map
Register
Read/Write Permission
Detail
Appendix A Modbus Map
Page 11
4824
Read or write
Reserved, unused
4825
Read or write
RF modem shutdown
1 = enable (on)(Default)
0 = shutdown (off)
4826
Read or write
Opto buffered input LED enable.
1 = enable (default)
0 = disable.
4827
Read or write
Battery charge voltage control.
0 = low rate (default) (approximately 14V)
1 = high rate (approximately 15V)
4828-4999
No read/write allowed
Reserved, unused
High Speed Counters
Two high speed counters are available at IN7 and IN8.
Register
Read/Write Permission
Detail
7001
Read and write
Pulse counter 1 on IN8
7002
Read and Write
Pulse counter 2 on IN7
Both counters count from 0 to 16,777,215.Maximum count rate is 3Khz (180,000 pulses/minute) with a 0-12V signal to
IN8 or IN7.
Pulse counters are reset by writing 0 to them.
Non-Volatile Floating Point Storage
Registers 7101 to 7356 store 32 bit floating point numbers.
Non-volatile storage has 1,000,000 write limitation.