Appendix a cx-10 modbus map – Remote Processing CX-10 User Manual
Page 43
Appendix A CX-10 Modbus Map
Appendix A Modbus Map
Page 10
Non-Volatile Setup
These are integer (16 bit) types. Function code 3 reads, 16 writes. All allow read and write. Address range is 4801 to 4999.
This group of registers dictate certain system setup conditions. They are non-volatile.
Register
Read/Write Permission
Detail
4801
Read or write
Reset non-volatile setup registers. Default value = 165. Writing a value other
than 165 to this register will cause the operating system to restore defaults to
registers 4801-4827. Restoration is performed on the next reset.
4802
Read or write
Clear non-volatile integer and floating point registers. Default value = 165.
Writing a value other than 165 to this register will cause the operating system
to write 0's to all non-volatile integer and floating point registers. Reset is
performed on the next reset.
4803-4809
Read or write
Reserved, unused
4810
Read or write
Define COM3 port operation as ASCII or modbus mode.
0 = ASCII mode
1 = modbus mode (default)
4811
Read or write
Modbus ID (0-255)
Default = 11
Current software will allow a 16 bit slave ID but will only use the lower 8 bits
(0-255).
4812
Read or write
Reserved, unused
4813
Read or write
COM3 baud rate
2 = 2400
3 = 4800
4 = 9600
5 = 19200 (default)
6 = 38400
7 = 57600
4814
Read or write
Reserved, unused
4815
Read or write
Modbus COM3 timer timout. Register value X 10 milli-seconds.
200 = 2 seconds (default)
When a print #3 message is sent, master mode will wait the amount of time
set in this register for data to start being received. If the message is not
recieved in time, the OS writes an error code 254 to register 4783. If data
starts coming into the buffer before the timeout expires, this register is no
longer in effect. Another 50 milli-second (fixed time) timeout takes over.
4816-20
Read or write
Reserved, unused
4821
Read or write
Reserved, unused
4822
Read or write
Reserved, unused
4823
Read or write
Switched V+ power control.
0 = Switched 12V & 5V off (default)
1 = Switched 12V & 5V ON