beautypg.com

Appendix a cx-10 modbus map – Remote Processing CX-10 User Manual

Page 38

background image

Appendix A CX-10 Modbus Map

Appendix A Modbus Map

Page 5

Hardware I/O Registers.
These are all integer (16 bit) types. Function code 3 reads, 16 writes.

Register

Read/write permission

Detail

1

Read only

Opto buffered digital inputs returned as bits 0-7

2

Read only

Spare - returns 0

3

Read only

Spare - returns 0

4

Read only

Spare - returns 0

5

Read only

Spare - returns 0

6

Read only

Spare - returns 0

7

Read only

Spare - returns 0

8

Read only

Charge/solar panel input. Multiply this number by 0.007326 to obtain volts.
Range is 0 - 30 volts.

9

Read only

Battery voltage. Multiply this number by 0.007326 to obtain volts.

10

Read or write

Relay on/off, set as bits 0-7. Write one word to control all 8 relays at the
same time. A 1 turns on a relay, 0 turns it off

11

Read only

Status of opto buffered input 1 (IN1)

12

Read only

Status of opto buffered input 2 (IN2)

13

Read only

Status of opto buffered input 3 (IN3)

14

Read only

Status of opto buffered input 4 (IN4)

15

Read only

Status of opto buffered input 5 (IN5)

16

Read only

Status of opto buffered input 6 (IN6)

17

Read only

Status of opto buffered input 6 (IN7)

18

Read only

Status of opto buffered input 6 (IN8)

19

Read or write

Relay 1 on/off. 1 = relay On, 0 = relay Off

20

Read or write

Relay 2 on/off. 1 = relay On, 0 = relay Off

21

Read or write

Relay 3 on/off. 1 = relay On, 0 = relay Off

22

Read or write

Relay 4 on/off. 1 = relay On, 0 = relay Off

23

Read or write

Relay 5 on/off. 1 = relay On, 0 = relay Off

24

Read or write

Relay 6 on/off. 1 = relay On, 0 = relay Off

25

Read or write

Relay 7 on/off. 1 = relay On, 0 = relay Off

26

Read or write

Relay 8 on/off. 1 = relay On, 0 = relay Off