Model PD650 Large Display Process Meter

Instruction Manual

72

Relays Operation

Overview

The relay capabilities of the meter expand its usefulness beyond simple
indication to provide users with alarm

ing

and control

ling

functions. These

capabilities include front panel alarm status LEDs as well as either 2 or 4 optional
relays. Typical applications include high or low temperature, level, pressure or
flow alarms, simple control applications like sump-pump or tank-filling and
automatic or manual batch controlling. There are four basic ways the relays can
be used:
1. High or Low Alarms
2. Simple On/Off Control with 100%

aA

djustable

Dd

eadband

3. Automatic Batch Control
4. Manual

Batch

Control

Relays Auto Initialization

When power is applied to the meter, the front panel LEDs and alarm relays will
reflect the state of the input to the meter. For instance, if the meter is powered up
and reads 500, the following table indicates how the alarm LEDs and relays will
react based on the various set and reset points:

Alarm #

HI or LO

Set

Point

Reset

Point

Power-up

Reading

Relay &

LED

1 HI

1000

500

499

Off

2 LO

700

900

500

On

3 LO

250

400

500

Off

4 HI

450

200

500

On

Fail-Safe Operation

The following table indicates how the relays behave based on Jumper J5 being
installed or not installed:

Jumper J5 on
Options Board

Fail-Safe

Relay Coils
Energized in

Power Failure

On

Enabled

Non-alarm state

Relays go to
alarm state

Off

Disabled

Alarm state

Relays go to
non-alarm state